Elevator 2 keeps stopping after its repair
ALT-2 · 24 Oct, 07:55 · Ground floor, Common areas (whole block)
Elevator 2 stopped 4 times in the last 7 days. Error DZ-04 (door zone fault) was logged in each stop. The same code was recorded on 9 Oct before repair #1 on 12 Oct, which was marked as fixed. The fault returned 9 days later.
Why it was raised
- Linked reports3
- Linked repairs1
- Device events5
Evidence connected
- Device eventDZ-04 logged on 9 Oct, before repair.9 Oct, 16:10
- Incident INC-1Same fault reported before the repair.9 Oct
- Repair R-1Repair on 12 Oct marked as fixed.12 Oct
- Incident INC-2Doors not closing, 21 Oct.21 Oct
- Device eventDZ-04 stop in the last 7 days.21 Oct, 13:03
- Device eventDZ-04 stop in the last 7 days.22 Oct, 07:48
- Device eventDZ-04 stop in the last 7 days.23 Oct, 17:54
- Incident INC-3Passengers trapped, 23 Oct.23 Oct
- Device eventDZ-04 stop in the last 7 days.24 Oct, 07:48
- EquipmentElevator 2
- ALT-2: Elevator 2 keeps stopping after its repair
What to check
- 1Have a qualified technician review the controller error log and compare it with the work done on 12 Oct. Check the door operator and door zone sensor.
A possible link, not a confirmed cause. A technician should verify on site.